Comprehensive Guide to the EPCOS BR5016 Power Factor Controller
The following data reflects the standard performance metrics for the BR 5016 / BR 5000 series: --- Epcos Power Factor Controller Br 5016 Manual Pdf
Prepare a standard cutout in the switchgear panel door matching the physical dimensions specified in the EPCOS manual. Insert the controller through the cutout from the front. Comprehensive Guide to the EPCOS BR5016 Power Factor
Up to 16 relay outputs, which are freely programmable for switching 3-phase capacitors. Current Measurement: Selectable through connection terminals. Sensitivity: depending on the setting. Dimensions: for panel mounting, with a door cutout requirement of Key Features and Functionality Current Measurement: Selectable through connection terminals
: If measuring voltage is connected L-L, phase shift programming may be required in the "Expert Mode" menu.
Tighten all screw terminal blocks. Loose connections cause thermal damage to the controller terminals and contactors. Downloading the Official PDF
When configuring the controller, ensure the is set according to the discharge devices of your capacitors (typically 60 seconds for EPCOS standard resistors). Setting a time too short can cause extremely high inrush currents, potentially leading to equipment damage or fire. Power Factor Controller - TDK Electronics